Haws®

Haws® AXION® 9201EW Emergency Tempering Thermostatic Mixing Valve, 5 in L, 1/2 in Inlet, Brass

260391 MFG #: 9201EW
$648.00 / ea
  • Type: Emergency Tempering
  • Nominal Size: 1/2
  • Dimensions: 5 in L x 1-5/8 in W x 3-1/2 in H
  • Flow Capacity: 1 to 10
  • Pressure Rating: 125
  • Top to Inlet Center: 1-3/8
  • Body Material: Brass
  • Media: Hot/Cold Water
  • End Style: FNPT
  • Temperature Rating: 85

Haws® AXION® Thermostatic Mixing Valve, Emergency Tempering, 1/2 in Inlet, 5 in Length, Brass

Model 9201EW (patent pending) is a thermostatic mixing valve that mixes hot and cold water to supply tempered water to a single emergency eye/face wash fixture requiring flow up to 10 gpm (37.8 L). Unit employs a paraffin filled thermostatic mixing element. Cold Water Bypass flow rate of 3.8 gpm (14.4 L). A 0.4 gpm (1.5 L) hot water flow if cold supply fails. The modular brass design with supplied check valves, oversized valve seats and a funnel design to improve temperature control with better mixing at low flow rates. Lime and calcium resistant components are used throughout. The outlet temperature factory setting is 85 deg F (29 deg C). Maximum operating pressure: 125 psi (8.62 Bar). Temperature adjustment range 60 - 90 deg F (16 - 32 deg C). Min/max inlet hot water temperature: 120 deg /180 deg F (49 deg /82 deg C), with recommended inlet temperature: 140 deg F (60 deg C). Min/max inlet cold water temperature: 40 deg /65 deg (4.4 deg /18.3 deg C). Inlets and outlet: 1/2 in FNPT.

QTY
  • Features
  • A flow rate of 1 to 10 gpm (3.8 to 37.8 L) for better temperature control across the operating range
  • Wax based thermostat technology for fast response time with proven highly reliable temperature control
  • Cold Water Bypass flow rate of 3.8 gpm (14.4 L) (When tested under conditions specified in ASSE 1071)
  • Modular brass design with supplied check valves
  • AXION® superior design and technology provide a complete safety solution for increased victim comfort
  • Over-sized valve seats resist failures caused by foreign matter
  • Efficient funnel design improves temperature control at low flow rates
  • Standard/Approvals: ASSE 1071, ANSI Z358.1, CSAus Certified, Meets requirements of the Buy American Act