Extended mix temperature range of 85-176 deg F (29-80 deg C)
Tamper-resistance cap
Low headloss
Outlet temperature strip
Note flow should never exceed standards for pipe size
2.3 CV, 1 gpm (3.8 lpm) min flow, 120-180 deg F (49-82 deg C) hot supply temperature
39 to 80 deg F (5 to 27 deg C) cold supply temperature
20% max variation in supply pressure
27 deg F (15 dg C) min. temperature differential between hot supply and mixed
85 to 175 deg F (29 to 80 deg C) outlet temperature range
(41 to 45 deg C) 115 to 120 deg F factory
Accuracy of outlet
+/- 3 deg F temperature
= 0.25% lead brass, noryl GFN2 internal components
Stainless steel spring
Varies (brass, CPVC, copper) fittings
EPDM gaskets, stainless steel temperature gauge, brass gauge fitting
5000 series allows for domestic hot water storage at temperatures high enough to increase the effective storage capacity of a water heater, kill harmful bacteria and still be delivered at a safe 120 deg F or less